LC1F265UD

Product ID:32846
Updated: 2026/4/4
schneider LC1F265UD

Key Features

  • 1Handle high currents up to 265A for robust motor control. 2、Switch voltages up to 600VAC for versatile power applications. 3、Ensure durability with the proven TeSys F Series design. 4、Simplify installation via panel mounting in industrial settings. 5、Meet international EN/IEC 60947-4-1 standards for safety.
Product Details
LC1F265UD
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC-1<br /><= 690 V AC-3<br /><= 690 V AC-4<br /><= 460 V DC
[Uc] control circuit voltage
250 V DC
[Ie] rated operational current
350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />265 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
350 A (at 104 °F (40 °C))
Rated breaking capacity
2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
2200 A 104 °F (40 °C) - 10 s<br />1230 A 104 °F (40 °C) - 30 s<br />950 A 104 °F (40 °C) - 1 min<br />620 A 104 °F (40 °C) - 3 min<br />480 A 104 °F (40 °C) - 10 min
Associated fuse rating
315 A aM at <= 440 V<br />400 A gG at <= 440 V
Average impedance
0.3 mOhm - Ith 350 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
37 W AC-1<br />21 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
132 kW at 380...400 V AC 50/60 Hz (AC-3)<br />140 kW at 415 V AC 50/60 Hz (AC-3)<br />140 kW at 440 V AC 50/60 Hz (AC-3)<br />160 kW at 500 V AC 50/60 Hz (AC-3)<br />160 kW at 660...690 V AC 50/60 Hz (AC-3)<br />147 kW at 1000 V AC 50/60 Hz (AC-3)<br />75 kW at 220...230 V AC 50/60 Hz (AC-3)<br />51 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in W
750 W 68 °F (20 °C))
Hold-in power consumption in W
5 W 68 °F (20 °C)
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
40...50 ms closing<br />40...65 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit connector 1 0.4 in² (240 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
5 W
Standards
EN 60947-1<br />JIS C8201-4-1<br />EN 60947-4-1<br />IEC 60947-1<br />IEC 60947-4-1
Product Certifications
RMRoS<br />DNV<br />CB<br />RINA<br />UL<br />BV<br />LROS (Lloyds register of shipping)<br />ABS<br />CCC
compatibility code
LC1F
Control circuit type
DC standard
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
8.0 in (203 mm)
Width
7.9 in (201.5 mm)
Depth
8.4 in (213 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
16.40 lb(US) (7.44 kg)

Specifications may be subject to change without notice