LC1F500N722L
Product ID:33028
Updated: 2026/4/4

Key Features
- 1Ensure high reliability in environments up to 55°C. 2、Control motors with a 3-pole, 600V, 500A nonreversing contactor. 3、Achieve high durability at 2400 cycles per hour. 4、Simplify installation using control circuit screw clamp terminals. 5、Support motor applications up to 250kW at 400V.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | TeSys F | Product or Component Type | Contactor |
| Device short name | LC1F | Contactor application | Motor control<br />Resistive load |
| Utilisation category | AC-4<br />AC-3<br />AC-1 | Poles description | 3P |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC | [Uc] control circuit voltage | 415 V AC 40...400 Hz |
| [Ie] rated operational current | 700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 | [Uimp] rated impulse withstand voltage | 8 kV |
| [Ith] conventional free air thermal current | 700 A (at 104 °F (40 °C)) | Rated breaking capacity | 4000 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 4200 A 104 °F (40 °C) - 10 s<br />3200 A 104 °F (40 °C) - 30 s<br />2400 A 104 °F (40 °C) - 1 min<br />1500 A 104 °F (40 °C) - 3 min<br />1200 A 104 °F (40 °C) - 10 min | Associated fuse rating | 500 A aM at <= 440 V<br />800 A gG at <= 440 V |
| Average impedance | 0.18 mOhm - Ith 700 A 50 Hz | [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C |
| Power dissipation per pole | 88 W AC-1<br />45 W AC-3 | Overvoltage category | III |
| power pole contact composition | 3 NO | Auxiliary contact composition | 2 NO + 2 NC |
| Motor power kW | 250 kW at 380...400 V AC 50/60 Hz (AC-3)<br />280 kW at 415 V AC 50/60 Hz (AC-3)<br />295 kW at 440 V AC 50/60 Hz (AC-3)<br />355 kW at 500 V AC 50/60 Hz (AC-3)<br />335 kW at 660...690 V AC 50/60 Hz (AC-3)<br />335 kW at 1000 V AC 50/60 Hz (AC-3)<br />147 kW at 220...230 V AC 50/60 Hz (AC-3)<br />80 kW at 400 V AC 50/60 Hz (AC-4) | motor power HP (UL / CSA) | 150 hp at 200 V AC<br />200 hp at 230 V AC<br />400 hp at 460 V AC<br />500 hp at 575 V AC |
| Control circuit voltage limits | Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C)) | Mechanical durability | 10 Mcycles |
| Inrush power in VA | 1100 VA, 40...400 Hz 0.9 68 °F (20 °C)) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Operating time | 40...65 ms closing<br />100...170 ms opening | Connections - terminals | Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection<br />Power circuit 2 bars 40 x 5 mm<br />Power circuit lugs-ring terminals 2 0.4 in² (240 mm²) |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m) | Mounting Support | Plate |
| Heat dissipation | 18 W | Standards | IEC 60947-4-1<br />EN 60947-4-1<br />JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-1 |
| Product Certifications | UL<br />CCC<br />DNV<br />LROS (Lloyds register of shipping)<br />BV<br />ABS<br />RMRoS<br />RINA<br />CB | Hold-in power consumption in VA | 18 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C)) |
| IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 | Protective treatment | TH |
| Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms<br />Vibrations contactor closed4 Gn, 5...300 Hz |
| Height | 15.7 in (400 mm) | Width | 9.2 in (233 mm) |
| Depth | 9.1 in (232 mm) | Operating altitude | 9842.52 ft (3000 m) without derating |
Specifications may be subject to change without notice