LC1F6304F7

Product ID:33039
Updated: 2026/4/4
schneider LC1F6304F7

Key Features

  • 1Control resistive loads up to 1000 A reliably. 2、Ensure safety with AC-1 utilization category compliance. 3、Utilize versatile 4-pole (4 NO) contact configuration. 4、Meet global standards including IEC 60947-4-1. 5、Optimize energy management in demanding applications.
Product Details
LC1F6304F7
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
110 V AC 40...400 Hz
[Ie] rated operational current
1000 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))<br />1250 A
Rated breaking capacity
5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5050 A 104 °F (40 °C) - 10 s<br />4400 A 104 °F (40 °C) - 30 s<br />3400 A 104 °F (40 °C) - 1 min<br />2200 A 104 °F (40 °C) - 3 min<br />1600 A 104 °F (40 °C) - 10 min
Associated fuse rating
1000 A gG at <= 440 V<br />630 A aM at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.25...0.5 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
5 Mcycles
Inrush power in VA
1650 VA, 40...400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA
22 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
1200 cyc/h 131 °F (55 °C)
Operating time
40...80 ms closing<br />100...200 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 60 x 5 mm<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 513.3 lbf.in (58 N.m)
Mounting Support
Plate
Heat dissipation
20 W
Standards
IEC 60947-4-1<br />JIS C8201-4-1<br />EN 60947-4-1<br />IEC 60947-1<br />EN 60947-1
Product Certifications
BV<br />UL<br />LROS (Lloyds register of shipping)<br />ABS<br />CB<br />RINA<br />CCC<br />RMRoS<br />DNV<br />UKCA
compatibility code
LC1F
Control circuit type
AC 40...400 Hz
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
12.0 in (304 mm)
Width
15.3 in (389 mm)
Depth
10.04 in (255 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
47.4 lb(US) (21.5 kg)

Specifications may be subject to change without notice