LC1G330EHEA
Product ID:37939
Updated: 2026/4/3

Key Features
- 1Deliver up to 200 kW power at 440V for demanding applications. 2、Utilize a 48-130V AC/DC wide band low-consumption electronic coil. 3、Monitor contact wear continuously with built-in Local and Remote CWD. 4、Save valuable panel space with compact 290x140x209 mm dimensions. 5、Ensure global compliance with CE, CB, CCC, cULus, EAC, KC, RCM, Marine certifications.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys Giga |
| Product or Component Type | Contactor | Device short name | LC1G |
| Contactor application | Power switching<br />Motor control | Utilisation category | AC-1<br />AC-3<br />AC-3e<br />AC-4<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />AC-8b<br />AC-8a<br />DC-1<br />DC-3<br />DC-5 |
| Poles description | 3P | [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC |
| [Ie] rated operational current | 440 A (at <104 °F (40 °C)) at <= 1000 V AC-1<br />330 A (at <140 °F (60 °C)) at <= 440 V AC-3 | [Uc] control circuit voltage | 48...130 V AC 50/60 Hz<br />48...130 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C)) | [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III | [Ith] conventional free air thermal current | 440 A (at 104 °F (40 °C)) |
| Rated breaking capacity | 2940 A at 440 V | [Icw] rated short-time withstand current | 2.65 kA - 10 s<br />1.8 kA - 30 s<br />1.3 kA - 1 min<br />0.9 kA - 3 min<br />0.75 kA - 10 min |
| Associated fuse rating | 400 A aM at <= 440 V for motor<br />250 A aM at <= 690 V for motor<br />500 A gG at <= 690 V | Average impedance | 0.000144 Ohm |
| [Ui] rated insulation voltage | 1000 V | Power dissipation per pole | 30 W AC-1 - Ith 440 A<br />16 W AC-3 - Ith 330 A |
| compatibility code | LC1G | Pole contact composition | 3 NO |
| Auxiliary contact composition | 1 NO + 1 NC | Motor power kW | 90 kW at 230 V AC 50/60 Hz (AC-3e)<br />160 kW at 400 V AC 50/60 Hz (AC-3e)<br />160 kW at 415 V AC 50/60 Hz (AC-3e)<br />185 kW at 440 V AC 50/60 Hz (AC-3e)<br />200 kW at 500 V AC 50/60 Hz (AC-3e)<br />220 kW at 690 V AC 50/60 Hz (AC-3e)<br />185 kW at 1000 V AC 50/60 Hz (AC-3e)<br />90 kW at 230 V AC 50/60 Hz (AC-3)<br />160 kW at 400 V AC 50/60 Hz (AC-3)<br />160 kW at 415 V AC 50/60 Hz (AC-3)<br />200 kW at 440 V AC 50/60 Hz (AC-3)<br />200 kW at 500 V AC 50/60 Hz (AC-3)<br />220 kW at 690 V AC 50/60 Hz (AC-3)<br />185 kW at 1000 V AC 50/60 Hz (AC-3)<br />90 kW at 230 V AC 50/60 Hz (AC-4)<br />160 kW at 400 V AC 50/60 Hz (AC-4)<br />160 kW at 415 V AC 50/60 Hz (AC-4)<br />185 kW at 440 V AC 50/60 Hz (AC-4)<br />200 kW at 500 V AC 50/60 Hz (AC-4)<br />220 kW at 690 V AC 50/60 Hz (AC-4)<br />185 kW at 1000 V AC 50/60 Hz (AC-4) |
| Maximum Horse Power Rating | 100 hp at 200/208 V 60 Hz<br />125 hp at 230/240 V 60 Hz<br />250 hp at 460/480 V 60 Hz<br />300 hp at 575/600 V 60 Hz | Irms rated making capacity | 3830 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting | Safety reliability level | B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles | inrush power in VA (50/60 Hz, AC) | 430 VA |
| inrush power in W (DC) | 360 W | hold-in power consumption in VA (50/60 Hz, AC) | 11.7 VA |
| hold-in power consumption in W (DC) | 9.0 W | Operating time | 40...70 ms closing<br />15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1<br />150 cyc/h AC-4 | Connections - terminals | Power circuit: bar 2 - busbar cross section: 32 x 10 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit: bolted connection<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end |
| Connection pitch | 1.8 in (45 mm) | Mounting Support | Plate |
| Standards | EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-1<br />UL 60335-2-40:Annex JJ | Product Certifications | CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL |
| Tightening torque | 309.8 lbf.in (35 N.m) | Height | 11.4 in (290 mm) |
| Width | 5.5 in (140 mm) | Depth | 8.9 in (226 mm) |
| Net Weight | 18.08 lb(US) (8.2 kg) | IP degree of protection | IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106 |
| Ambient Air Temperature for Operation | -13…140 °F (-25…60 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed | color | Dark grey |
| Protective treatment | TH | Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) at Uc |
Specifications may be subject to change without notice