LC1G6304EHEN
Product ID:38249
Updated: 2026/4/3

Key Features
- 1Handle high currents up to 1050A @440V for AC-1. 2、Save panel space with a compact 324x280x248mm design. 3、Enhance reliability using bidirectional peak limiting coil tech. 4、Meet global standards with CE, CB, CCC, cULus, EAC, KC, RCM, Marine certs. 5、Monitor contact wear continuously via Local CWD and alarms.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys Giga |
| Product or Component Type | Contactor | Device short name | LC1G |
| Contactor application | Power switching | Utilisation category | AC-3<br />AC-3e<br />AC-1<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />DC-1<br />DC-3<br />DC-5 |
| Poles description | 4P | [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC |
| [Ie] rated operational current | 630 A (at <140 °F (60 °C)) at <= 440 V AC-3<br />1050 A (at <104 °F (40 °C)) at <= 1000 V AC-1 | [Uc] control circuit voltage | 48...130 V AC 50/60 Hz<br />48...130 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C)) | [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III | [Ith] conventional free air thermal current | 1050 A (at 104 °F (40 °C)) |
| Rated breaking capacity | 5550 A at 440 V | [Icw] rated short-time withstand current | 5.05 kA - 10 s<br />4.4 kA - 30 s<br />3.4 kA - 1 min<br />2.2 kA - 3 min<br />1.6 kA - 10 min |
| Associated fuse rating | 630 A aM at <= 440 V for motor<br />500 A aM at <= 690 V for motor<br />1250 A gG at <= 690 V | Average impedance | 0.000065 Ohm |
| [Ui] rated insulation voltage | 1000 V | Power dissipation per pole | 70 W AC-1 - Ith 1050 A<br />26 W AC-3 - Ith 630 A |
| compatibility code | LC1G | Pole contact composition | 4 NO |
| Auxiliary contact composition | 1 NO + 1 NC | Irms rated making capacity | 7220 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting | Safety reliability level | B10d = 100000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 1800000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles | inrush power in VA (50/60 Hz, AC) | 990 VA |
| inrush power in W (DC) | 790 W | hold-in power consumption in VA (50/60 Hz, AC) | 18.7 VA |
| hold-in power consumption in W (DC) | 9.5 W | Operating time | 40...70 ms closing<br />15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1 | Connections - terminals | Power circuit: bar 2 - busbar cross section: 52 x 20 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end |
| Connection pitch | 2.8 in (70 mm) | Mounting Support | Plate |
| Standards | EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />UL 60335-1<br />UL 60335-2-40:Annex JJ | Product Certifications | CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL |
| Tightening torque | 513.3 lbf.in (58 N.m) | Height | 11.2 in (284 mm) |
| Width | 11.06 in (281 mm) | Depth | 10.5 in (266 mm) |
| Net Weight | 39.7 lb(US) (18 kg) | IP degree of protection | IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106 |
| Ambient Air Temperature for Operation | -13…140 °F (-25…60 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed | color | Dark grey |
| Protective treatment | TH | Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) at Uc |
Specifications may be subject to change without notice