LC1K09105B7

Product ID:37972
Updated: 2026/4/3
schneider LC1K09105B7

Key Features

  • 1Utilize a compact design with DIN-rail compatibility for easy installation. 2、Control motors rated up to 4kW at 400V AC3, 9A reliably. 3、Operate with a built-in 24V 50/60Hz AC coil for non-inductive loads. 4、Benefit from an integrated 1NO auxiliary contact for control circuit signaling. 5、Ensure compliance with global standards including IEC, UL, CSA, and CCC.
Product Details
LC1K09105B7
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
TeSys K
Range
TeSys
Product or Component Type
Contactor
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-1<br />AC-4<br />AC-3
Poles description
3P
Pole contact composition
3 NO
[Ie] rated operational current
16 A (at <122 °F (50 °C)) at <= 440 V AC AC-1 for power circuit<br />9 A at <= 440 V AC AC-3 for power circuit
Auxiliary contact composition
1 NO
Control circuit type
AC 50/60 Hz
Motor power kW
2.2 kW 220...230 V AC 50/60 Hz AC-3<br />4 kW 380...415 V AC 50/60 Hz AC-3<br />4 kW 440 V AC 50/60 Hz AC-3<br />4 kW 480 V AC 50/60 Hz AC-3<br />4 kW 500...600 V AC 50/60 Hz AC-3<br />4 kW 660...690 V AC 50/60 Hz AC-3<br />2.2 kW 400 V AC 50/60 Hz AC-4
Auxiliary contacts type
Instantaneous 1 NO
[Uc] control circuit voltage
24 V AC 50/60 Hz
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <122 °F (50 °C))<br />Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C))
Overvoltage category
III
Standards
EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ
Protective treatment
TC IEC 60068<br />TC DIN 50016
Flame retardance
V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102
Connections - terminals
solder pins 1.5 x 0.9 mm
[Ith] conventional free air thermal current
16 A (at 122 °F (50 °C)) for power circuit<br />10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110<br />110 A AC for power circuit conforming to IEC 60947<br />110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity
110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947
Associated fuse rating
25 A gG at <= 440 V for power circuit<br />25 A aM for power circuit<br />10 A gG for signalling circuit conforming to IEC 60947<br />10 A gG for signalling circuit conforming to VDE 0660
Average impedance
3 mOhm - Ith 16 A 50 Hz for power circuit
Inrush power in VA
30 VA (at 68 °F (20 °C))
Hold-in power consumption in VA
4.5 VA (at 68 °F (20 °C))
Heat dissipation
1.3 W
Operating time
10...20 ms coil de-energisation and NO opening<br />10...20 ms coil energisation and NO closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Maximum operating rate
3600 cyc/h
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Height
2.3 in (58 mm)
Width
1.8 in (45 mm)
Depth
2.2 in (57 mm)
Product Certifications
CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA
Operating altitude
6561.68 ft (2000 m) without derating

Specifications may be subject to change without notice