LC2K09004E7
Product ID:32866
Updated: 2026/4/4

Key Features
- 1Ensure reliable switching with a robust 4P design for AC-1 applications. 2、Handle voltages up to 440V and currents up to 10A for high-power needs. 3、Minimize energy consumption using an efficient 48VA coil for operation. 4、Meet safety standards with RoHS compliance and overvoltage category III. 5、Apply to various resistive load scenarios for versatile industrial power control.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Product name | TeSys K |
| Product or Component Type | Changeover contactor | Device short name | LC2K |
| Device Application | Control | Contactor application | Resistive load |
| Utilisation category | AC-1 | Device presentation | Preassembled with reversing power busbar |
| Poles description | 4P | power pole contact composition | 4 NO |
| [Ue] rated operational voltage | Power circuit 690 V AC 50/60 Hz | [Ie] rated operational current | 20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit |
| Control circuit type | AC 50/60 Hz | [Uc] control circuit voltage | 48 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV | Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 140 °F (60 °C)) for power circuit | Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947 | [Icw] rated short-time withstand current | 90 A 122 °F (50 °C) - 1 s for power circuit<br />85 A 122 °F (50 °C) - 5 s for power circuit<br />80 A 122 °F (50 °C) - 10 s for power circuit<br />60 A 122 °F (50 °C) - 30 s for power circuit<br />45 A 122 °F (50 °C) - 1 min for power circuit<br />40 A 122 °F (50 °C) - 3 min for power circuit<br />20 A 122 °F (50 °C) - >= 15 min for power circuit |
| Associated fuse rating | 25 A gG at <= 440 V for power circuit<br />25 A aM for power circuit | Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit 600 V UL 508<br />Power circuit 690 V IEC 60947-4-1<br />Power circuit 600 V CSA C22.2 No 14 | Electrical durability | 0.16 Mcycles 20 A AC-1 <= 690 V |
| Interlocking type | Mechanical | Mounting Support | Plate<br />Rail |
| Standards | EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1 | Product Certifications | CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA |
| Connections - terminals | screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid<br /> screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end<br /> screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end<br /> screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid<br /> screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end<br /> screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end | Tightening torque | 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2<br /> 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm |
| Operating time | 10...20 ms coil energisation and NO closing<br />10...20 ms coil de-energisation and NO opening | Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles | Maximum operating rate | 3600 cyc/h |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at <122 °F (50 °C))<br />Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C)) | Inrush power in VA | 30 VA (at 68 °F (20 °C)) |
| Hold-in power consumption in VA | 4.5 VA (at 68 °F (20 °C)) | Heat dissipation | 1.3 W |
| IP degree of protection | IP20 VDE 0106 | Protective treatment | TC IEC 60068<br />TC DIN 50016 |
| Ambient Air Temperature for Operation | -13…122 °F (-25…50 °C) | Ambient Air Temperature for Storage | -58…176 °F (-50…80 °C) |
| Operating altitude | 6561.68 ft (2000 m) without derating | Flame retardance | V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27<br />Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6<br />Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 | Height | 2.3 in (58 mm) |
| Width | 3.5 in (90 mm) | Depth | 2.2 in (57 mm) |
| Net Weight | 0.84 lb(US) (0.38 kg) |
Specifications may be subject to change without notice