RM17UB310

Product ID:33339
Updated: 2026/4/3
schneider RM17UB310

Key Features

  • 1Set precise delay times from 0.3 to 30 seconds for control. 2、Detect overvoltage and undervoltage between phases and neutral. 3、Ensure long-term performance with a 502.2-year MTTFd. 4、Mount easily on 35 mm symmetrical DIN rails. 5、Operate within a wide 183-528V AC range.
Product Details
RM17UB310
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Harmony Control Relays
Relay Type
Voltage control relay
Product or Component Type
3-phase control relay
Product Specific Application
For 3-phase supply
Relay name
RM17UB3
Relay monitored parameters
Overvoltage and undervoltage between phases
time delay
Adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
Switching capacity in VA
1250 VA
Measurement range
220...480 V AC
Contacts type and composition
1 C/O
Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
Minimum switching current
10 mA 5 V DC
Maximum switching current
5 A AC/DC
Supply voltage limits
183…528 V AC
Power consumption in VA
0…22 VA 400 V AC 50 Hz
Control circuit frequency
50...60 Hz +/- 10 %
Voltage detection threshold
183 V
Output contacts
1 C/O
Nominal output current
5 A
Hysteresis
2 %
Measurement accuracy
+/- 10 % of the full scale value
delay at power up
650 ms
Maximum measuring cycle
150 ms measurement cycle as true rms value
Threshold adjustment voltage
2...20 % of Un selected<br />-2...-17 % in the range 220 V AC<br />+2...+10 % in the range 480 V AC<br />-2...-12 % in the range 208 V AC
Repeat accuracy
+/- 0.5 % input and measurement circuit<br />+/- 1 % time delay
Measurement error
< 1 % over the whole range with voltage variation<br />0.05 %/°C with temperature variation
Response time
< 200 ms (in the event of a fault)
Quality labels
CE
Insulation resistance
> 500 MOhm 500 V DC IEC 60255-5<br />> 500 MOhm 500 V DC IEC 60664-1
Operating position
Any position without derating
Local signalling
for power ON LED (green)<br /> for relay ON LED (yellow)
Overvoltage category
III IEC 60664-1
[Ui] rated insulation voltage
400 V IEC 60664-1
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end<br />Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end<br />Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end<br />Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Tightening torque
5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material
Self-extinguishing plastic
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Utilisation category
AC-12 IEC 60947-5-1<br />AC-13 IEC 60947-5-1<br />AC-14 IEC 60947-5-1<br />AC-15 IEC 60947-5-1<br />DC-12 IEC 60947-5-1<br />DC-13 IEC 60947-5-1<br />DC-14 IEC 60947-5-1
[Un] rated nominal voltage
, self-powered
Safety reliability data
B10d = 470000<br />MTTFd = 502.2 years
Control Type
Without test button
Width
0.7 in (17.5 mm)
Net Weight
0.18 lb(US) (0.08 kg)
Electromagnetic compatibility
Emission standard for industrial environments conforming to IEC 61000-6-4<br />Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3<br />Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Ambient air temperature for operation
-4…122 °F (-20…50 °C)
Vibration resistance
0.35 mm 5…57.6 Hz)IEC 60068-2-6<br />1 gn 57.6…150 Hz)IEC 60255-21-1
Shock resistance
5 gn IEC 60068-2-27
Standards
IEC 60255-1
Product Certifications
GOST<br />UL<br />GL<br />C-tick<br />CSA
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Relative humidity
95 % 131 °F (55 °C) IEC 60068-2-30
IP degree of protection
IP20 IEC 60529 terminals)<br />IP30 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Directives
89/336/EEC - electromagnetic compatibility<br />73/23/EEC - low voltage directive
Dielectric test voltage
2 kV AC 50 Hz, 1 min
Non-dissipating shock wave
4 kV

Specifications may be subject to change without notice