RXM2AB1UD
Product ID:33478
Updated: 2026/4/3

Key Features
- 1Achieve 100,000 mechanical and electrical cycles for resistive loads. 2、Switch 12A loads with a fast 20ms operating and reset time. 3、Verify status easily using the lockable test button and LED indicator. 4、Meet global standards including CE, CSA, GOST, UL, RoHS, and REACH. 5、Support sustainability through extended product life and recyclability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony Relay | Series name | Miniature |
| Product or Component Type | Plug-in relay | Device short name | RXM |
| Contacts type and composition | 2 C/O | [Uc] control circuit voltage | 250 V DC |
| Status LED | Without | Control Type | Lockable test button |
| Utilisation coefficient | 20 % | Shape of pin | Flat |
| [Ui] rated insulation voltage | 250 V IEC | [Uimp] rated impulse withstand voltage | 4 kV 1.2/50 µs |
| Contacts material | AgNi | [Ie] rated operational current | 3 A 28 V DC) NC IEC<br />3 A 250 V AC) NC IEC<br />6 A 28 V DC) NO IEC<br />6 A 250 V AC) NO IEC |
| Continuous output current | 10 A | Maximum switching voltage | 250 V IEC |
| resistive rated load | 6 A 250 V AC<br />6 A 28 V DC | Maximum switching capacity | 1500 VA/168 W |
| Minimum switching capacity | 170 mW 10 mA, 17 V | Operating rate | <= 1200 cycles/hour under load<br /><= 18000 cycles/hour no-load |
| Mechanical durability | 10000000 cycles | Electrical durability | 200000 cycles resistive |
| average coil consumption | 1 W | Drop-out voltage threshold | >= 0.1 Uc |
| operate time | 20 ms | release time | 20 ms |
| average coil resistance | 62500 Ohm 20 °C +/- 10 % | Rated operational voltage limits | 200...275 V DC |
| Safety reliability data | B10d = 100000 | Protection category | RT I |
| Operating position | Any position | Net Weight | 0.082 lb(US) (0.037 kg) |
| Device presentation | Complete product | Dielectric strength | 1300 V AC between contacts with micro disconnection<br />2000 V AC between coil and contact with basic insulation<br />2000 V AC between poles with basic insulation |
| Product Certifications | UL<br />Lloyd's<br />CE<br />CSA<br />GOST<br />IECEE CB Scheme | Standards | IEC 61810-1 |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Ambient air temperature for operation | -40…104 °F (-40…40 °C) |
| Vibration resistance | 3 gn +/- 1 mm 10…150 Hz)5 cycles in operation<br />5 gn +/- 1 mm 10…150 Hz)5 cycles not operating | IP degree of protection | IP40 conforming to IEC 60529 |
| Shock resistance | 10 gnin operation<br />30 gnnot operating | Pollution degree | 3 |
Specifications may be subject to change without notice