RXM2AB2ED

Product ID:33487
Updated: 2026/4/3
schneider RXM2AB2ED

Key Features

  • 1Test circuits securely with the lockable test button. 2、Handle 12A loads at 250VAC for robust control. 3、Enhance safety via magnetically isolated contacts. 4、Simplify installation using pre-assembled relay solutions. 5、Connect multiple relays easily with the included bus jumper.
Product Details
RXM2AB2ED
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Harmony Electromechanical Relays
Series name
Miniature
Product or Component Type
Plug-in relay
Device short name
RXM
Contacts type and composition
2 C/O
[Uc] control circuit voltage
48 V DC
Status LED
With
Control Type
Lockable test button
Utilisation coefficient
20 %
Shape of pin
Flat
[Ui] rated insulation voltage
250 V IEC<br />300 V CSA<br />300 V UL
[Uimp] rated impulse withstand voltage
4 kV 1.2/50 µs
Contacts material
AgNi
[Ie] rated operational current
12 A 28 V DC) NO IEC<br />12 A 250 V AC) NO IEC<br />6 A 28 V DC) NC IEC<br />6 A 250 V AC) NC IEC<br />12 A 28 V DC) UL<br />12 A 277 V AC) UL
Continuous output current
10 A
Maximum switching voltage
250 V IEC
resistive rated load
12 A 250 V AC<br />12 A 28 V DC
Maximum switching capacity
3000 VA/336 W
Minimum switching capacity
170 mW 10 mA, 17 V
Operating rate
<= 1200 cycles/hour under load<br /><= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles resistive
average coil consumption
0.9 W
Drop-out voltage threshold
>= 0.1 Uc
operate time
20 ms
release time
20 ms
average coil resistance
2560 Ohm 20 °C +/- 10 %
Rated operational voltage limits
38.4...52.8 V DC
Safety reliability data
B10d = 100000
Protection category
RT I
Test levels
Level A group mounting
Operating position
Any position
CAD overall height
3.3 in (82.8 mm)
CAD overall depth
3.16 in (80.35 mm)
Net Weight
0.082 lb(US) (0.037 kg)
Device presentation
Complete product
Dielectric strength
1300 V AC between contacts with micro disconnection<br />2000 V AC between coil and contact with basic insulation<br />2000 V AC between poles with basic insulation
Product Certifications
UL<br />Lloyd's<br />CE<br />CSA<br />GOST<br />IECEE CB Scheme
Standards
CSA C22.2 No 14<br />IEC 61810-1<br />UL 508
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient air temperature for operation
-40…131 °F (-40…55 °C)
Vibration resistance
3 gn +/- 1 mm 10…150 Hz)5 cycles in operation<br />5 gn +/- 1 mm 10…150 Hz)5 cycles not operating
IP degree of protection
IP40 conforming to IEC 60529
Shock resistance
10 gnin operation<br />30 gnnot operating
Pollution degree
3

Specifications may be subject to change without notice