TM5CAI8O8CL

Product ID:34046
Updated: 2026/4/5
schneider TM5CAI8O8CL

Key Features

  • 1Integrate 8 analog inputs and 8 analog outputs in a compact design. 2、Ensure precise measurement with 4-20 mA signal compatibility. 3、Achieve high accuracy using 12-bit resolution for data. 4、Benefit from reliable performance backed by a 3-year warranty. 5、Simplify industrial automation system expansion and control.
Product Details
TM5CAI8O8CL
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Compact I/O expansion block
Enclosure Material
Plastic
Color
White
Input/output number
16
Input/output number of splitter box
8 I + 8 O
Number of modules
Analog input 2 x 4<br />Analog output 2 x 4
Analogue input number
8
Analogue input range
0...20 mA<br />4...20 mA
Analogue input resolution
12 bits current
Analogue output number
8
Analogue output type
Current 8
Analogue output range
0...20 mA
Input filtering
<= 50 ms not configurable
Sampling duration
20 ms input/output for the whole module<br />5 ms input/output per channel
Response time
<= 1 ms status change output
Maximum leakage current
5 µA when switched off) output
Protection type
Short-circuit output
Isolation
No insulation between channels<br />500 Vrms AC insulation between channel and bus
Current consumption
8 mA 5 V DC bus<br />217 mA 24 V DC input/output
Power dissipation in W
5.25 W
Local signalling
for power supply 4 LEDs (green)<br /> for power supply 4 LEDs (red)<br /> for output status 8 LEDs (yellow)<br /> for input status 8 LEDs (green)
Electrical Connection
Removable spring terminal block
Surge withstand
0.5 kV differential mode 24 V DC EN/IEC 61000-4-5<br />1 kV common mode 24 V DC EN/IEC 61000-4-5
Mounting Support
DIN rail
Net Weight
0.55 lb(US) (0.25 kg)
Standards
CSA C22.2 No 213<br />UL 508<br />CSA C22.2 No 142<br />IEC 61131-2
Product Certifications
CSA<br />C-tick<br />GOST-R<br />UL
marking
CE
Ambient air temperature for operation
14…122 °F (-10…50 °C) vertical installation)<br />14…140 °F (-10…60 °C) horizontal installation)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Relative Humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact EN/IEC 61000-4-2<br />8 kV in air EN/IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz EN/IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz EN/IEC 61000-4-3
Resistance to fast transients
1 kV EN/IEC 61000-4-4 I/O)<br />1 kV EN/IEC 61000-4-4 shielded cable)<br />2 kV EN/IEC 61000-4-4 power lines)
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11 zone B - class A

Specifications may be subject to change without notice