  • 1Acquire signals reliably with two digital input channels. 2、Operate flexibly across a wide 100-240V AC voltage range. 3、Ensure safety with hardware filters and short-circuit protection. 4、Integrate easily into systems with a compact 25-gram design. 5、Reduce downtime through robust industrial-grade construction.
Product Details
TM5SDI2A
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Discrete input module
Discrete input number
2
Discrete input voltage
100...240 V
Range Compatibility
Modicon LMC058<br />PacDrive LMC motion controller<br />Modicon M258
Product Compatibility
PacDrive LMC Pro<br />Motion controller<br />PacDrive LMC Pro 2<br />Logic controller<br />PacDrive LMC Eco
Discrete input voltage type
AC
input voltage limits
100...240 V
Discrete input current
5…11 mA
Color
Black
Input filtering
<= 25 ms configurable by software<br /><= 30 ms hardware from state 1 to state 0<br /><= 40 ms hardware from state 0 to state 1
Protection Type
Short-circuit protection
Isolation
No insulation between channels<br />2500 V AC insulation between channel and bus for 1 minute
Maximum voltage drop
<2 V at 500 mA sensor supply
Maximum supply current for sensors
500 mA
Current consumption
28 mA 5 V DC bus
Maximum power dissipation in W
0.69 W
Local signalling
1 LED green power supply<br />1 LED red power supply<br />2 LEDs green input status
Electrical connection
3 wires
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2
Product Certifications
GOST-R<br />CSA<br />C-tick<br />cULus
Ambient air temperature for operation
14…131 °F (-10…55 °C) without derating horizontal installation)<br />14…140 °F (-10…60 °C) with derating factor horizontal installation)<br />14…122 °F (-10…50 °C) vertical installation)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Relative Humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact EN/IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air EN/IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz EN/IEC 61000-4-3<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz EN/IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O EN/IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable EN/IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines EN/IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode EN/IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode EN/IEC 61000-4-5<br />Conducted RF disturbances EN/IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11