TM5SDI2DFS
Product ID:34161
Updated: 2026/4/4

Key Features
- 1Ensure reliable safety operations with two dedicated digital input channels. 2、Customize input filters via software for precise signal management. 3、Utilize two test outputs for comprehensive system validation. 4、Operate at 24 VDC for versatile industrial control integration. 5、Meet key safety standards including EN ISO 13849 PL e and SIL 3.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon TM5 | Product or Component Type | Safety dc discrete input module |
| Discrete input number | 2 | Discrete input voltage | 24 V |
| Range Compatibility | Modicon M258<br />Modicon LMC058<br />PacDrive LMC motion controller | Product Compatibility | Motion controller<br />PacDrive LMC Pro 2<br />Logic controller<br />PacDrive LMC Pro<br />PacDrive LMC Eco |
| Discrete input voltage type | DC | input voltage limits | 20.4...28.8 V |
| Discrete input logic | Sink | Discrete input current | 3.45 mA |
| input impedance | 7 kOhm | Color | Red |
| Voltage state 0 guaranteed | <= 5 V | Voltage state 1 guaranteed | >= 15 V |
| Input filtering | <= 500 ms configurable by software<br /><= 150 ms hardware | Protection Type | Short-circuit protection<br />Overload protection |
| Isolation | 500 Vrms AC insulation between channel and bus<br />No insulation between channels | Maximum voltage drop | <0.6 V at 100 mA |
| Maximum supply current for sensors | 300 mA | Maximum power consumption in W | 1 W internal<br />0.25 W bus |
| Local signalling | 1 LED green power supply<br />1 LED red power supply<br />2 LEDs green/red input status<br />2 LEDs red safety status | Electrical connection | 2 wires |
| marking | CE | Safety level | SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1 |
| Safety reliability data | MTTFd > 100 years<br />PFD < 1E-5<br />PFH < 1E-9 | Net Weight | 0.055 lb(US) (0.025 kg) |
| Standards | CSA C22.2 No 142<br />EN 13849-1<br />IEC 62061<br />UL 508<br />IEC 61131-2<br />IEC 61508 | Product Certifications | CSA<br />cULus<br />GOST-R |
| Ambient air temperature for operation | 14…122 °F (-10…50 °C) vertical installation)<br />14…131 °F (-10…55 °C) horizontal installation)<br />14…140 °F (-10…60 °C) | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
| Relative Humidity | 5…95 % without condensation | IP degree of protection | IP20IEC 60529 |
| Pollution degree | 2 IEC 60664 | Operating altitude | 0...6561.68 ft (0...2000 m) |
| Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) | Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail |
| Shock resistance | 15 gn 11 ms | Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |
Specifications may be subject to change without notice