TM5SDM4DTRFS
Product ID:34168
Updated: 2026/4/4

Key Features
- 1Meet SIL 3/PL e safety standards for critical applications. 2、Ensure reliable operation with 24VDC and 6A relay contacts. 3、Configure input filters via software for signal stability. 4、Operate from -10 to 55°C in harsh industrial environments. 5、Integrate easily with Modicon TM5 and PacDrive systems.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon TM5 | Product or Component Type | Safety discrete I/O module |
| Discrete input number | 2 | Discrete input voltage | 24 V |
| Discrete output number | 2 | Discrete output type | Relay |
| Range Compatibility | PacDrive LMC motion controller | Product Compatibility | PacDrive LMC Pro<br />PacDrive LMC Pro 2<br />PacDrive LMC Eco |
| Discrete input voltage type | DC | input voltage limits | 20.4...28.8 V |
| Discrete input logic | Sink | Discrete input current | 3.3 mA |
| input impedance | 7.3 kOhm | Output voltage | 24 V DC |
| Output voltage limits | 20.4...28.8 V | Discrete output logic | Source |
| Color | Red | Voltage state 0 guaranteed | <= 5 V |
| Voltage state 1 guaranteed | >= 15 V | Input filtering | <= 500 ms configurable by software<br /><= 150 ms hardware |
| Protection Type | Short-circuit protection<br />Overload protection | Isolation | No insulation between channels<br />500 Vrms AC insulation between channel and bus |
| Maximum power consumption in W | 1.15 W internal<br />0.26 W bus | Local signalling | 1 LED green power supply<br />1 LED red power supply<br />2 LEDs green/red input status<br />2 LEDs red safety status<br />2 LEDs red/orange output status |
| Electrical connection | 2 wires | marking | CE |
| Safety level | SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1 | Safety reliability data | MTTFd > 100 years<br />PFD < 1E-5<br />PFH < 1E-9 |
| Net Weight | 0.055 lb(US) (0.025 kg) | Standards | CSA C22.2 No 142<br />IEC 62061<br />IEC 61131-2<br />IEC 61508<br />UL 508<br />EN 13849-1 |
| Product Certifications | CSA<br />cULus<br />GOST-R | Ambient air temperature for operation | 14…122 °F (-10…50 °C) vertical installation)<br />14…131 °F (-10…55 °C) horizontal installation) |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Relative Humidity | 5…95 % without condensation |
| IP degree of protection | IP20IEC 60529 | Pollution degree | 2 IEC 60664 |
| Operating altitude | 0...6561.68 ft (0...2000 m) | Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) |
| Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail | Shock resistance | 15 gn 11 ms |
| Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |