TM5SDO4T
Product ID:34180
Updated: 2026/4/4

Key Features
- 1Integrate flexibly into complex machines using remote or distributed IO islands. 2、Supervise operations locally and distantly with embedded diagnostic capabilities. 3、Swap I/O modules without system shutdown to simplify maintenance procedures. 4、Set up cabling easily with spring terminals or removable terminal blocks. 5、Ensure reliable operation with reverse polarity, short circuit, and overload protection.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon TM5 | Product or Component Type | Discrete output module |
| Discrete output number | 4 | Discrete output type | Transistor |
| Range Compatibility | Modicon LMC058<br />PacDrive LMC motion controller<br />Modicon M258 | Product Compatibility | PacDrive LMC Pro 2<br />PacDrive LMC Pro<br />PacDrive LMC Eco<br />Logic controller<br />Motion controller |
| Output voltage | 24 V DC | Output voltage limits | 20.4...28.8 V |
| Discrete output logic | Source | Current per channel | 0.5 A |
| Maximum current per output common | 2 A | Color | White |
| Peak output current | 12 A | Switching frequency | <= 500 Hz resistive |
| Response time | <= 300 µs from state 0 to state 1 output<br /><= 300 µs from state 1 to state 0 output | Maximum leakage current | 5 µA when switched off |
| Protection Type | Reverse polarity protection<br />Short-circuit protection<br />Overload protection | Isolation | 500 Vrms AC insulation between channel and bus<br />No insulation between channels |
| Maximum voltage drop | <0.3 V at 500 mA output<br /> <2 V at 500 mA sensor supply | Maximum supply current for sensors | 500 mA |
| Current consumption | 20 mA 24 V DC input/output<br />32 mA 5 V DC bus | Maximum power dissipation in W | 0.86 W |
| Local signalling | 1 LED green power supply<br />1 LED red power supply<br />4 LEDs yellow output status | Electrical connection | 3 wires |
| marking | CE | Net Weight | 0.055 lb(US) (0.025 kg) |
| Standards | IEC 61131-2<br />CSA C22.2 No 213<br />UL 508<br />CSA C22.2 No 142 | Product Certifications | CSA<br />GOST-R<br />cULus<br />C-tick |
| Ambient air temperature for operation | 14…131 °F (-10…55 °C) without derating horizontal installation)<br />14…140 °F (-10…60 °C) with derating factor horizontal installation)<br />14…122 °F (-10…50 °C) vertical installation) | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
| Relative Humidity | 5…95 % without condensation | IP degree of protection | IP20IEC 61131-2 |
| Pollution degree | 2 IEC 60664 | Operating altitude | 0...6561.68 ft (0...2000 m) |
| Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) | Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail |
| Shock resistance | 15 gn 11 ms | Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz IEC 61000-4-3<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |
Specifications may be subject to change without notice