TM5SE1IC20005

Product ID:34069
Updated: 2026/4/5
schneider TM5SE1IC20005

Key Features

  • 1Achieve 4 MHz high-speed counting for rapid motion control. 2、Integrate seamlessly with PacDrive LMC Eco, Pro, and Pro2 controllers. 3、Ensure precise measurement with 16/32-bit counter input resolution. 4、Support efficient processing with a 2 ms maximum cycle time. 5、Enhance system safety with 500 Vrms AC channel-to-bus insulation.
Product Details
TM5SE1IC20005
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Counter module
Function of module
2 x 24 V DC RS422 sink auxiliary inputs<br />24 V DC encoder power supply
Discrete input number
2
Counting frequency
4 MHz
Encoder type
1 incremental encoder
Range Compatibility
PacDrive LMC Eco<br />PacDrive LMC Pro<br />PacDrive LMC Pro2
Product Compatibility
Motion controller
Counter inputs resolution
16 bits/32 bits
Maximum cycle time
2 ms
Isolation
500 Vrms AC insulation between channel and bus
Discrete input logic
Sink
Discrete input voltage
24 V DC
Discrete input current
24 V
Input filtering
<= 200 ms
Current consumption
2 mA 5 V DC bus<br />63 mA 24 V DC input/output
Maximum power dissipation in W
1.51 W
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2
Product Certifications
cULus<br />C-tick<br />GOST-R<br />CSA
Ambient air temperature for operation
32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact EN/IEC 61000-4-2<br />8 kV in air EN/IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz EN/IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz EN/IEC 61000-4-3
Resistance to fast transients
1 kV EN/IEC 61000-4-4 I/O)<br />1 kV EN/IEC 61000-4-4 shielded cable)<br />2 kV EN/IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode EN/IEC 61000-4-5<br />1 kV common mode EN/IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11

Specifications may be subject to change without notice