Key Features

  • 1Support 16 thermocouple inputs for types B, E, J, K, L, N, R, S, T, U.
  • 2Deliver precise measurements with 16-bit analog-to-digital conversion.
  • 3Ensure reliable operation with 1000 Vrms channel and bus isolation.
  • 4Integrate easily using a compact, standard module format.
  • 5Meet IEC, DIN, and RoHS compliance standards for global use.

Need price and lead time?

Request a quote for original schneider TSXAEY1614C. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Analog input module
Analogue input number
16
Analogue input type
Thermocouple thermocouple B<br />Thermocouple thermocouple E<br />Thermocouple thermocouple J<br />Thermocouple thermocouple K<br />Thermocouple thermocouple L<br />Thermocouple thermocouple N<br />Thermocouple thermocouple R<br />Thermocouple thermocouple S<br />Thermocouple thermocouple T<br />Thermocouple thermocouple U<br />Voltage +/- 80 mV
Analog/digital conversion
16 bits
Nominal read cycle time
70 ms per channel
Measurement error
0.8 °C thermocouple E 25 °C<br />0.9 °C thermocouple J 25 °C<br />0.9 °C thermocouple L 25 °C<br />1 °C thermocouple K 25 °C<br />1 °C thermocouple T 25 °C<br />1 °C thermocouple U 25 °C<br />1.1 °C thermocouple N 25 °C<br />1.2 °C thermocouple E 0...60 °C<br />1.3 °C thermocouple T 0...60 °C<br />1.3 °C thermocouple U 0...60 °C<br />1.4 °C thermocouple J 0...60 °C<br />1.4 °C thermocouple L 0...60 °C<br />1.6 °C thermocouple K 0...60 °C<br />1.7 °C thermocouple N 0...60 °C<br />2.1 °C thermocouple R 25 °C<br />2.2 °C thermocouple S 25 °C<br />2.4 °C thermocouple R 0...60 °C<br />2.5 °C thermocouple B 25 °C<br />3.7 °C thermocouple S 0...60 °C<br />4 °C thermocouple B 0...60 °C
Isolation between channels and bus
1000 Vrms
Isolation between channels and ground
1000 Vrms
Common mode between channels
250 V AC or 280 V AC
Common mode between channels and earth
250 V DC
Input overvoltage protection
-15…15 V at state 0 250 Ohm<br />-30…30 V at state 1 250 Ohm
Electrical connection
2 connectors SUB-D 25
Overcurrent
-30…30 mA at state 1 250 kOhm
marking
CE
Current consumption
300 mA 5 V DC
Module format
Standard
Net Weight
0.77 lb(US) (0.35 kg)
Standards
IEC 751<br />DIN 43760<br />IEC 584<br />DIN 43710<br />NFC 42-330<br />IEC 1131
Product Certifications
GL<br />RINA<br />LR<br />RMRS<br />BV<br />ABS<br />DNV
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
Conformal coating Humiseal 1A33<br />TC
IP Degree of Protection
IP20
Pollution degree
2