TSXAEY810C
Product ID:34408
Updated: 2026/4/4

Key Features
- 1Process 8 low-level analog signals with 16-bit precision. 2、Ensure reliable integration with Modicon Premium PLCs. 3、Provide isolation between channels and system bus. 4、Achieve fast read cycles down to 3.3 ms per channel. 5、Receive peace of mind with a 2-year warranty.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Premium Automation platform | Product or Component Type | Analog input module |
| Input level | Low level | Analogue input number | 8 |
| Analogue input type | Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V | Analog/digital conversion | 16 bits |
| Nominal read cycle time | 29.7 ms | Fast read cycle time | 3.3 ms + 3.3 ms x number of channels used |
| Measurement error | 0.12 % of full scale 0...20 mA 0...60 °C<br />0.12 % of full scale 4...20 mA 0...60 °C<br />0.13 % of full scale 0...5 V 25 °C<br />0.13 % of full scale 1...5 V 25 °C<br />0.142 % of full scale 0...20 mA 25 °C<br />0.142 % of full scale 4...20 mA 25 °C<br />0.191 % of full scale 0...5 V 0...60 °C<br />0.191 % of full scale 1...5 V 0...60 °C<br />0.244 % of full scale +/- 10 V 25 °C<br />0.244 % of full scale 0...10 V 25 °C<br />0.305 % of full scale +/- 10 V 0...60 °C<br />0.305 % of full scale 0...10 V 0...60 °C | Isolation between channels and bus | 1000 Vrms |
| Isolation between channels and ground | 1000 Vrms | Isolation between channels | +/- 200 V |
| Common mode between channels | +/- 200 | Input overvoltage protection | -15…15 V at state 0 250 Ohm<br />-30…30 V at state 1 250 Ohm |
| Electrical connection | 1 connector SUB-D 25 | Overcurrent | -30…30 mA at state 1 250 kOhm |
| marking | CE | Current consumption | 475 mA 5 V DC |
| Module format | Standard | Net Weight | 0.73 lb(US) (0.33 kg) |
| Standards | IEC 1131 | Product Certifications | RMRS<br />ABS<br />RINA<br />GL<br />DNV<br />LR<br />BV |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Relative Humidity | 10…95 % without condensation for operation<br />5…95 % without condensation for storage | Operating altitude | 0...6561.68 ft (0...2000 m) |
| Protective treatment | Conformal coating Humiseal 1A33<br />TC | IP Degree of Protection | IP20 |
| Pollution degree | 2 |
Specifications may be subject to change without notice