Key Features
- 1Process 8 low-level analog signals with 16-bit precision.
- 2Ensure reliable integration with Modicon Premium PLCs.
- 3Provide isolation between channels and system bus.
- 4Achieve fast read cycles down to 3.3 ms per channel.
- 5Receive peace of mind with a 2-year warranty.
Need a quote? Enter your quantity and get pricing fast.
Qty
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Premium Automation platform | Product or Component Type | Analog input module |
| Input level | Low level | Analogue input number | 8 |
| Analogue input type | Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V | Analog/digital conversion | 16 bits |
| Nominal read cycle time | 29.7 ms | Fast read cycle time | 3.3 ms + 3.3 ms x number of channels used |
| Measurement error | 0.12 % of full scale 0...20 mA 0...60 °C<br />0.12 % of full scale 4...20 mA 0...60 °C<br />0.13 % of full scale 0...5 V 25 °C<br />0.13 % of full scale 1...5 V 25 °C<br />0.142 % of full scale 0...20 mA 25 °C<br />0.142 % of full scale 4...20 mA 25 °C<br />0.191 % of full scale 0...5 V 0...60 °C<br />0.191 % of full scale 1...5 V 0...60 °C<br />0.244 % of full scale +/- 10 V 25 °C<br />0.244 % of full scale 0...10 V 25 °C<br />0.305 % of full scale +/- 10 V 0...60 °C<br />0.305 % of full scale 0...10 V 0...60 °C | Isolation between channels and bus | 1000 Vrms |
| Isolation between channels and ground | 1000 Vrms | Isolation between channels | +/- 200 V |
| Common mode between channels | +/- 200 | Input overvoltage protection | -15…15 V at state 0 250 Ohm<br />-30…30 V at state 1 250 Ohm |
| Electrical connection | 1 connector SUB-D 25 | Overcurrent | -30…30 mA at state 1 250 kOhm |
| marking | CE | Current consumption | 475 mA 5 V DC |
| Module format | Standard | Net Weight | 0.73 lb(US) (0.33 kg) |
| Standards | IEC 1131 | Product Certifications | RMRS<br />ABS<br />RINA<br />GL<br />DNV<br />LR<br />BV |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Relative Humidity | 10…95 % without condensation for operation<br />5…95 % without condensation for storage | Operating altitude | 0...6561.68 ft (0...2000 m) |
| Protective treatment | Conformal coating Humiseal 1A33<br />TC | IP Degree of Protection | IP20 |
| Pollution degree | 2 |
Specifications may be subject to change without notice