TSXDEY16A4

Product ID:34331
Updated: 2026/4/4
schneider TSXDEY16A4

Key Features

  • 1Deploy 16 isolated channels for extensive sensor connectivity. 2、Ensure reliable signal acquisition with 12 mA input current. 3、Connect seamlessly to 2-wire or 3-wire proximity sensors. 4、Meet strict standards including EN/IEC 61131-2 and CSA. 5、Operate robustly with 0.83 W power dissipation.
Product Details
TSXDEY16A4
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Discrete input module
Discrete input number
16 capacitive isolated EN/IEC 61131-2 type 2
Discrete input voltage
110 V AC
Network frequency
50/60 Hz 47…63 Hz AC
Sensor power supply
85…132 V
Input compatibility
With 2-wire/3-wire proximity sensors EN/IEC 60947-5-2
Discrete input current
12 mA
Voltage state 1 guaranteed
74 V
Current state 1 guaranteed
6 mA
Voltage state 0 guaranteed
20 V
Current state 0 guaranteed
4 mA
Input impedance
9200 Ohm at state 1
Response Time
10 ms<br /><= 20 ms
isalotion resistance
< 10 MOhm 500 V DC
Power dissipation
0.83 W
Electrical Connection
Screw terminal
marking
CE
Current consumption
80 mA 5 V DC
Module format
Standard
Net Weight
0.71 lb(US) (0.32 kg)
Dielectric strength
1500 V AC 50/60 Hz
Standards
93/68/EEC<br />CSA C22.2 No 213 Class I Division 2 Group C<br />EN/IEC 61131-2<br />73/23/EEC<br />CSA C22.2 No 142<br />89/336/EEC<br />UL 508<br />CSA C22.2 No 213 Class I Division 2 Group A<br />IEC 60664<br />CSA C22.2 No 213 Class I Division 2 Group B<br />92/31/EEC<br />CSA C22.2 No 213 Class I Division 2 Group D
Product Certifications
DNV<br />ABS<br />RINA<br />GL<br />LR<br />BV<br />RMRS
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2

Specifications may be subject to change without notice