Key Features
- 1Reduce energy consumption by up to 30% with high-efficiency design. 2、Save panel space using the compact, easy-to-install footprint. 3、Extend operational lifespan via advanced thermal management systems. 4、Ensure compliance and safety by meeting all key industry standards. 5、Simplify integration with broad compatibility across electrical systems.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony XB4 | Product or Component Type | Emergency stop push-button<br />Emergency switching off push-button |
| Device short name | XB4 | Bezel material | Chromium plated metal |
| Fixing collar material | Zamak | Mounting diameter | 0.9 in (22.5 mm) |
| Sale per indivisible quantity | 1 | Shape of signaling unit head | Round |
| Type of operator | trigger action and mechanical latching | Head type | Standard |
| Reset | Turn to release | Operator profile | Red mushroom Ø 40 mm, unmarked |
| Contact operation | Slow-break | Connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1<br />Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1 |
| Height | 1.9 in (47 mm) | Width | 1.6 in (40 mm) |
| Depth | 3.2 in (82 mm) | Terminals description ISO n°1 | (13-14)NO |
| Resistance to high pressure washer | 1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m | Contacts type and composition | 2 NC + 1 NO |
| Contacts usage | Standard contacts | Positive opening | With IEC 60947-5-1 appendix K |
| Operating travel | 0.06 in (1.5 mm) NC changing electrical state)<br />0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel) | Mechanical durability | 300000 cycles |
| Tightening torque | 7.08…10.6 lbf.in (0.8…1.2 N.m) IEC 60947-1 | Shape of screw head | Cross Philips no 1<br />Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm |
| Contacts material | Silver alloy (Ag/Ni) | Short-circuit protection | 10 A cartridge fuse gG IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A IEC 60947-5-1 | [Ui] rated insulation voltage | 600 V 3)IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-1 | [Ie] rated operational current | 3 A 240 V, AC-15, A600 IEC 60947-5-1<br />6 A 120 V, AC-15, A600 IEC 60947-5-1<br />0.1 A 600 V, DC-13, Q600 IEC 60947-5-1<br />0.27 A 250 V, DC-13, Q600 IEC 60947-5-1<br />0.55 A 125 V, DC-13, Q600 IEC 60947-5-1<br />1.2 A 600 V, AC-15, A600 IEC 60947-5-1 |
| Electrical durability | 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C | Electrical reliability | Λ < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4 |
| Device presentation | Complete product | Protective treatment | TH |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) |
| Electrical shock protection class | Class I IEC 60536 | IP degree of protection | IP66 IEC 60529<br />IP69<br />IP69K |
| NEMA degree of protection | NEMA 13<br />NEMA 4X | IK degree of protection | IK06 conforming to IEC 50102 |
| Standards | ISO 13850<br />IEC 60947-1<br />IEC 60947-5-5<br />IEC 60364-5-53<br />IEC 60947-5-4<br />IEC 60204-1<br />UL 508<br />IEC 60947-5-1<br />CSA C22.2 No 14<br />JIS C8201-5-1<br />JIS C8201-1 | Product Certifications | CSA<br />LROS (Lloyds register of shipping)<br />BV<br />UL Listed<br />DNV |
| Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 | Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Specifications may be subject to change without notice