XB5FG61C0
Product ID:35673
Updated: 2026/4/7

Key Features
- 1Ensure continuous operation with robust components under demanding conditions. 2、Optimize for minimal energy loss to reduce costs and environmental impact. 3、Prevent electrical shocks and fires with multiple safety mechanisms. 4、Save space in industrial and commercial settings with a compact design. 5、Build to last using durable materials and rigorous testing protocols.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony XB5 | Product or Component Type | Selector switch |
| Device short name | XB5F | Bezel material | Plastic colour plated grey |
| Head type | Built-in-flush | Mounting diameter | 1.2 in (30.5 mm) |
| Sale per indivisible quantity | 1 | Shape of signaling unit head | Round |
| Type of operator | Right to left spring return | Operator profile | Black key switch, unmarked |
| Operator position information | 2 positions 90° | Type of Keylock | Key 455 |
| Contacts type and composition | 1 NO | Contact operation | Slow-break |
| Connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1<br />Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1 | Height | 1.7 in (42 mm) |
| Width | 1.4 in (36.6 mm) | Depth | 3.9 in (98.5 mm) |
| Terminals description ISO n°1 | (13-14)NO | Resistance to high pressure washer | 1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m |
| Key withdrawal position | Left | Contacts usage | Standard contacts |
| Positive opening | Without | Mechanical durability | 1000000 cycles |
| Tightening torque | 7.08…10.6 lbf.in (0.8…1.2 N.m) IEC 60947-1 | Shape of screw head | Cross Philips no 1<br />Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm |
| Contacts material | Silver alloy (Ag/Ni) | Short-circuit protection | 10 A cartridge fuse gG IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A IEC 60947-5-1 | [Ui] rated insulation voltage | 600 V 3)IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-1 | [Ie] rated operational current | 3 A 240 V, AC-15, A600 IEC 60947-5-1<br />6 A 120 V, AC-15, A600 IEC 60947-5-1<br />0.1 A 600 V, DC-13, Q600 IEC 60947-5-1<br />0.27 A 250 V, DC-13, Q600 IEC 60947-5-1<br />0.55 A 125 V, DC-13, Q600 IEC 60947-5-1<br />1.2 A 600 V, AC-15, A600 IEC 60947-5-1 |
| Electrical durability | 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C | Electrical reliability | Λ < 10exp(-6) 5 V, 1 mA in clean environment IEC 60947-5-4<br />Λ < 10exp(-8) 17 V, 5 mA in clean environment IEC 60947-5-4 |
| Device presentation | Complete product | Protective treatment | TH |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) |
| Electrical shock protection class | Class II IEC 60536 | IP degree of protection | IP66 IEC 60529<br />IP67 |
| NEMA degree of protection | NEMA 13<br />NEMA 4X | IK degree of protection | IK03 conforming to IEC 50102 |
| Standards | IEC 60947-1<br />UL 508<br />JIS C8201-5-1<br />IEC 60947-5-4<br />IEC 60947-5-1<br />CSA C22.2 No 14<br />JIS C8201-1 | Product Certifications | UL Listed<br />CSA |
| Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 | Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Specifications may be subject to change without notice