XB5FVB1
Product ID:35735
Updated: 2026/4/7

Key Features
- 1Withstand severe environments with IP66, IP67, and IP69K ingress protection ratings. 2、Prevent vibration issues with secure contact and head designs for reliable mounting. 3、Connect easily via USB or RJ45 ports and adjust settings with an integrated timer. 4、Ensure clear visual signaling with pilot lights, illuminated pushbuttons, and selector switches. 5、Visualize data quickly with basic or configurable displays for faster mounting.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony XB5 | Product or Component Type | Pilot light |
| Device short name | XB5F | Bezel material | Dark grey plastic |
| Fixing collar material | Plastic | Head type | Built-in-flush |
| Mounting diameter | 1.2 in (30.5 mm) | Sale per indivisible quantity | 1 |
| Shape of signaling unit head | Round | cap/operator or lens colour | White |
| Operator additional information | With plain lens | Light source | Universal LED |
| Bulb base | Integral LED | Light source colour | White |
| [Us] rated supply voltage | 24 V AC/DC 50/60 Hz | Device presentation | Complete product |
| Height | 1.7 in (42 mm) | Width | 1.4 in (36.6 mm) |
| Depth | 2.2 in (55 mm) | Terminals description ISO n°1 | (X1-X2)PL |
| Net Weight | 0.084 lb(US) (0.038 kg) | Resistance to high pressure washer | 1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m |
| Connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1<br />Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end IEC 60947-1 | [Ui] rated insulation voltage | 250 V 3)IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV IEC 60947-1 | Signalling type | Steady |
| GCR BRIDGE | XB5FVCUST01 | compatibility code | XB5 |
| Supply voltage limits | 19.2…30 V DC<br />21.6…26.4 V AC | current consumption | 18 mA |
| Service life | 100000 h at rated voltage and 25 °C | Surge withstand | 1 kV IEC 61000-4-5 |
| Protective treatment | TH | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
| Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) | Overvoltage category | Class II IEC 60536 |
| IP degree of protection | IP66 IEC 60529<br />IP67 IEC 60529<br />IP69 IEC 60529<br />IP69K ISO 20653 | NEMA degree of protection | NEMA 13<br />NEMA 4X |
| IK degree of protection | IK03 conforming to IEC 50102 | Standards | JIS C8201-5-1<br />CSA C22.2 No 14<br />UL 508<br />IEC 60947-1<br />IEC 60947-5-4<br />IEC 60947-5-1<br />JIS C8201-1<br />ISO 21702<br />ISO 22196:2011 |
| Product Certifications | UL Listed<br />CSA | Vibration resistance | 5 gn 12…500 Hz)IEC 60068-2-6 |
| Shock resistance | 50 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />30 gn 11 ms) half sine wave acceleration IEC 60068-2-27 | Resistance to fast transients | 2 kV IEC 61000-4-4 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) IEC 61000-4-3 | Electromagnetic compatibility | Electrostatic discharge - test level: 6 kV (on contact (on metal parts)) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2<br />Electromagnetic emission class B conforming to IEC 55011 |
| Resistance to electrostatic discharge | 6 kV on contact (on metal parts) IEC 61000-4-2<br />8 kV in free air (in insulating parts) IEC 61000-4-2 | Electromagnetic emission | Class B IEC 55011 |
Specifications may be subject to change without notice