ZB4BW0B534

Product ID:24285
Updated: 2026/4/4
schneider ZB4BW0B534

Key Features

  • 1Integrate orange LED illumination for superior visibility in low-light conditions. 2、Achieve compact installations with a 30 mm width and 47 mm height design. 3、Ensure long-term reliability with 5,000,000 mechanical operation cycles. 4、Meet EN/IEC 60947-1 and -5-1 safety standards for electrical compliance. 5、Simplify integration through compatibility with Harmony XB4 pilot lights.
Product Details
ZB4BW0B534
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Harmony XB4
Product or Component Type
Complete body/contact assembly and light block
Device short name
ZB4
Fixing collar material
Zamak
Sale per indivisible quantity
1
Head type
Standard
Contacts type and composition
2 NO
Contact operation
Slow-break
Connections - terminals
Plug-in connector
Light source
Protected LED
Bulb base
Integral LED
Light block supply
Direct
Light source colour
Orange
[Us] rated supply voltage
24 V AC/DC 50/60 Hz
CAD overall width
1.2 in (30 mm)
CAD overall height
1.9 in (47 mm)
Terminals description ISO n°1
(13-14)NO
Contacts usage
Standard
Positive opening
Without
Operating travel
0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel)
Operating force
2.3 N NO changing electrical state
Operating torque
0.44 lbf.in (0.05 N.m) NO changing electrical state
Mechanical durability
5000000 cycles
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
4 A cartridge fuse gG EN/IEC 60947-5-1
[Ith] conventional free air thermal current
10 A EN/IEC 60947-5-1
[Ui] rated insulation voltage
250 V 3)EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
4 kV EN 60947-1
[Ie] rated operational current
3 A 240 V, AC-15, A300 EN/IEC 60947-5-1<br />6 A 120 V, AC-15, A300 EN/IEC 60947-5-1<br />0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1<br />0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1
Electrical durability
1000000 cycles, AC-15, 1 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 1.5 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.15 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
Electrical reliability
Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4
Signalling type
Steady
Supply voltage limits
19.2…30 V DC<br />21.6…26.4 V AC
current consumption
18 mA
Service life
100000 h at rated voltage and 25 °C
Surge withstand
1 kV IEC 61000-4-5
Protective treatment
TH
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-40…158 °F (-40…70 °C)
Electrical shock protection class
Class I IEC 60536
Standards
JIS C8201-5-1<br />CSA C22.2 No 14<br />UL 508<br />EN/IEC 60947-5-4<br />EN/IEC 60947-5-5<br />EN/IEC 60947-1<br />EN/IEC 60947-5-1<br />JIS C8201-1
Product Certifications
UL Listed<br />CSA<br />GL<br />LROS (Lloyds register of shipping)<br />BV<br />DNV
Vibration resistance
5 gn 2…500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Resistance to fast transients
2 kV IEC 61000-4-4
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3
Resistance to electrostatic discharge
6 kV on contact (on metal parts) IEC 61000-2-6<br />8 kV in free air (in insulating parts) IEC 61000-2-6
Electromagnetic emission
Class B IEC 55011

Specifications may be subject to change without notice