ZB4BW0G414
Product ID:24354
Updated: 2026/4/4

Key Features
- 1Ensure safety with a protected LED light source and integral bulb base. 2、Install flexibly using a 1 x 0.22 to 2 x 16 AWG wire range. 3、Provide reliable and secure slow break contact operation. 4、Utilize robust construction designed for demanding industrial use. 5、Enhance visibility with clear red illumination in various environments.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony XB4 | Product or Component Type | Complete body/contact assembly and light block |
| Device short name | ZB4 | Fixing collar material | Zamak |
| Sale per indivisible quantity | 1 | Contacts type and composition | 1 NO |
| Contact operation | Slow-break | Connections - terminals | Plug-in connector |
| Light source | Protected LED | Bulb base | Integral LED |
| Light block supply | Direct | Light source colour | Red |
| [Us] rated supply voltage | 110...120 V AC 50/60 Hz | CAD overall width | 1.2 in (30 mm) |
| CAD overall height | 1.9 in (47 mm) | Terminals description ISO n°1 | (13-14)NO |
| Contacts usage | Standard | Positive opening | Without |
| Operating travel | 0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel) | Operating force | 2.3 N NO changing electrical state |
| Operating torque | 0.44 lbf.in (0.05 N.m) NO changing electrical state | Mechanical durability | 5000000 cycles |
| Contacts material | Silver alloy (Ag/Ni) | Short-circuit protection | 4 A cartridge fuse gG EN/IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A EN/IEC 60947-5-1 | [Ui] rated insulation voltage | 250 V 3)EN/IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV EN 60947-1 | [Ie] rated operational current | 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1<br />6 A 120 V, AC-15, A300 EN/IEC 60947-5-1<br />0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1<br />0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1 |
| Electrical durability | 1000000 cycles, AC-15, 1 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 1.5 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.15 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C | Electrical reliability | Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4 |
| Signalling type | Steady | current consumption | 14 mA |
| Service life | 100000 h at rated voltage and 25 °C | Surge withstand | 1 kV IEC 61000-4-5 |
| Protective treatment | TH | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
| Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) | Electrical shock protection class | Class I IEC 60536 |
| Standards | EN/IEC 60947-5-4<br />EN/IEC 60947-5-1<br />EN/IEC 60947-5-5<br />EN/IEC 60947-1<br />CSA C22.2 No 14<br />JIS C8201-5-1<br />UL 508<br />JIS C8201-1 | Product Certifications | LROS (Lloyds register of shipping)<br />GL<br />DNV<br />UL Listed<br />CSA<br />BV |
| Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 | Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
| Resistance to fast transients | 2 kV IEC 61000-4-4 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) IEC 61000-4-3 |
| Resistance to electrostatic discharge | 6 kV on contact (on metal parts) IEC 61000-2-6<br />8 kV in free air (in insulating parts) IEC 61000-2-6 | Electromagnetic emission | Class B IEC 55011 |
Specifications may be subject to change without notice