schneider ZB4BZ1414

Key Features

  • 1Achieve 5 million mechanical cycles with durable silver alloy contacts. 2、Ensure compliance with EN/IEC, UL, CSA, and other global standards. 3、Simplify installation using the snap-fit head and single-screw mounting. 4、Withstand harsh industrial environments thanks to robust construction. 5、Secure reliable performance with a 250V insulation voltage rating.
Product Details
ZB4BZ1414
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Harmony XB4
Product or Component Type
Complete body/contact assembly
Device short name
ZB4
Fixing collar material
Zamak
Sale per indivisible quantity
1
Head type
Standard
Contacts type and composition
1 NO + 2 NC
Contact operation
Slow-break
Contact block type
Single
Device Composition
Fixing collar<br />Body
Connections - terminals
Plug-in connector
CAD overall width
1.2 in (30 mm)
CAD overall height
1.9 in (47 mm)
CAD overall depth
1.5 in (37 mm)
Terminals description ISO n°1
(11-12)NC
Net Weight
0.141 lb(US) (0.064 kg)
Contacts usage
Standard contacts
Positive opening
With EN/IEC 60947-5-1 appendix K
Operating travel
0.06 in (1.5 mm) NC changing electrical state)<br />0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel)
Operating torque
0.44 lbf.in (0.05 N.m) NO changing electrical state
Mechanical durability
5000000 cycles
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
4 A cartridge fuse gG EN/IEC 60947-5-1
[Ith] conventional free air thermal current
10 A EN/IEC 60947-5-1
[Ui] rated insulation voltage
250 V 3)EN 60947-1
[Uimp] rated impulse withstand voltage
4 kV EN 60947-1
[Ie] rated operational current
3 A 240 V, AC-15, A300 EN/IEC 60947-5-1<br />6 A 120 V, AC-15, A300 EN/IEC 60947-5-1<br />0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1<br />0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1
Electrical durability
10000000 cycles, AC-15, 1 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />10000000 cycles, AC-15, 1.5 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />10000000 cycles, AC-15, 3 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />10000000 cycles, DC-13, 0.15 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />10000000 cycles, DC-13, 0.4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
Electrical reliability
Λ < 10exp(-6) 5 V, 1 mA in clean environment EN/IEC 60947-5-4<br />Λ < 10exp(-8) 17 V, 5 mA in clean environment EN/IEC 60947-5-4
Protective treatment
TH
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-40…158 °F (-40…70 °C)
IP degree of protection
IP20 IEC 60529
Standards
EN/IEC 60947-1<br />CSA C22.2 No 14<br />EN/IEC 60947-5-1<br />JIS C8201-5-1<br />UL 508<br />EN/IEC 60947-5-5<br />EN/IEC 60947-5-4<br />JIS C8201-1
Product Certifications
DNV<br />CSA<br />BV<br />LROS (Lloyds register of shipping)<br />GL<br />UL
Vibration resistance
5 gn 2…500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27

Specifications may be subject to change without notice