schneider ZB6ZB52B

Key Features

  • 1Achieve IP65 protection for reliable use in harsh environments.
  • 2Install on small machines, control panels, and surveillance rooms.
  • 3Utilize silver alloy contacts for dependable electrical operation.
  • 4Fit into applications where mounting surface area is restricted.
  • 5Meet IEC, UL, CSA, and CCC standards for safety compliance.

Need price and lead time?

Request a quote for original schneider ZB6ZB52B. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Harmony XB6
Product or Component Type
Complete body for illuminated push-button
Device short name
ZB6
Fixing collar material
Plastic
Sale per indivisible quantity
1
Contacts type and composition
1 NC
Contact operation
Slow-break
Connections - terminals
Faston connector 2.8 x 0.5 mm
Light source
LED
Bulb base
Integral LED
Light source colour
Yellow
[Us] rated supply voltage
12...24 V AC/DC
CAD overall width
0.9 in (24 mm)
CAD overall height
0.7 in (18 mm)
CAD overall depth
2.008 in (51 mm)
Terminals description ISO n°1
(11-12)NC
Net Weight
0.013 lb(US) (0.006 kg)
Contacts usage
Standard
Positive opening
With EN/IEC 60947-5-1 appendix K
Operating travel
0.04 in (1 mm) NC changing electrical state)<br />0.2 in (4.3 mm) total travel)
Operating force
2.5 N NC changing electrical state
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
6 A cartridge fuse gG EN/IEC 60947-5-1
[Ui] rated insulation voltage
250 V 3)EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
4 kV EN/IEC 60947-1
[Ie] rated operational current
3 A 120 V, AC-15, B300<br />1.5 A 240 V, AC-15, B300<br />0.1 A 250 V, DC-13, R300<br />0.22 A 125 V, DC-13, R300
Electrical durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
Electrical reliability
Λ = 10exp(-8) 5 V 1 mA with confidence level of 90 % EN/IEC 60947-5-4
Signalling type
Steady
Supply voltage limits
6…30 V AC/DC
current consumption
15 mA
Surge withstand
1 kV direct contact IEC 61000-4-5<br />2 kV in free air IEC 61000-4-5
Protective treatment
TC
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-13…158 °F (-25…70 °C)
Electrical shock protection class
Class II IEC 61140
Standards
JIS C 4520<br />EN/IEC 60947-1<br />UL 508<br />CSA C22.2 No 14<br />EN/IEC 60947-5-1<br />EN/IEC 60947-5-5<br />JIS C 852
Product Certifications
GOST<br />UL<br />CSA<br />CCC
Vibration resistance
+/- 3 mm 2…500 Hz)IEC 60068-2-6<br />5 gn 2…500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Resistance to fast transients
2 kV IEC 61000-4-4
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3
Resistance to electrostatic discharge
6 kV on contact (on metal parts) IEC 61000-2-6<br />8 kV in free air (in insulating parts) IEC 61000-2-6
Electromagnetic emission
Class B IEC 55011

Specifications may be subject to change without notice