ZBE1016TQ
Product ID:27633
Updated: 2026/4/7

Key Features
- 1Achieve fast and easy assembly and disassembly. 2、Withstand harsh industrial environments with robust construction. 3、Ensure reliable switching with durable silver alloy contacts. 4、Connect versatilely using compatible screw clamp terminals. 5、Deploy in high-reliability industrial applications confidently.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Harmony XB5<br />Harmony XB4 | Product or Component Type | Contact block |
| Device short name | ZBE | Sale per indivisible quantity | 100 |
| IP degree of protection | IP20 IEC 60529 | Contact operation | Slow-break |
| Contact block type | Single | Contacts usage | Low power switching contacts |
| Connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end EN 60947-1<br />Screw clamp terminals, >= 1 x 0.22 mm² without cable end EN 60947-1 | Contacts type and composition | 1 NO |
| Positive opening | Without | Operating travel | 0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel) |
| Operating force | 2.3 N NO changing electrical state | Mechanical durability | 10000000 cycles |
| Tightening torque | 7.08…10.6 lbf.in (0.8…1.2 N.m) EN 60947-1 | Shape of screw head | Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm |
| Contacts material | Gold flashed (Ag/Ni/Au) contacts | Short-circuit protection | 10 A cartridge fuse gG EN/IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A EN/IEC 60947-5-1 | [Ui] rated insulation voltage | 600 V 3)EN 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV EN 60947-1 | [Ie] rated operational current | 3 A 240 V, AC-15, A600 EN/IEC 60947-5-1<br />6 A 120 V, AC-15, A600 EN/IEC 60947-5-1<br />0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1<br />0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1<br />0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1<br />1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1 |
| Electrical durability | 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C | Mounting of block | Front mounting |
| Electrical composition code | C1 9)<br />C2 7)<br />C3 6)<br />C4 4)<br />C5 5)<br />C6 3)<br />C7 4)<br />C8 2)<br />C9 3)<br />C12 6)<br />M1 6)<br />M2 4)<br />M3 4)<br />M5 2)<br />M6 2)<br />M7 6)<br />M8 4)<br />M9 2)<br />SF1 3)<br />SF2 2)<br />MF1 2)<br />MF2 2)<br />C10 2)<br />M4 2)<br />C13 1) | Protective treatment | TH |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) |
| Standards | EN/IEC 60947-5-1<br />CSA C22.2 No 14<br />JIS C8201-5-1<br />UL 508<br />EN/IEC 60947-5-4<br />EN/IEC 60947-1<br />JIS C8201-1 | Product Certifications | UL<br />DNV<br />GOST<br />BV<br />CCC<br />GL<br />CSA<br />LROS (Lloyds register of shipping) |
| Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 | Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Specifications may be subject to change without notice