3VA1112-3EE42-0AA0
Product ID:122682
Updated: 2026/4/8

Key Features
- 1Deliver reliable line protection with a 25 kA breaking capacity at 415V. 2、Suit various 4-pole configurations with integrated TM220 and ATFM protection systems. 3、Provide precise overload protection, adjustable from 88A to 125A for safe operation. 4、Ensure comprehensive safety with short-circuit protection set at 10 times the rated current. 5、Withstand harsh environments from -25°C to 70°C for up to 20,000 cycles.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Int interrupting Capacity Ics(kA): @400V or 415V | 25 | Rated Voltage(V): | 690 |
| Number of Poles: | 4P | Description | 3VA1N160 R125 TM220 F/4P; 3VA1_160 dimensions; Rated current 125A; Interrupting rating N: 25 kA; Trip unit TM220; |
| Mounting Method: | F: Fixed Mounting | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM220 [L adjustable, I fixed] |
| Rated Ultimate Breaking Capacity Icu(kA): @400V or 415V | 25 | Interrupting Rating: | N: 25 kA |
| Rated Current In(A): | 125 | Specifications: | 160 [1-160A] |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA1112-3EE42-0AA0 |
Specifications may be subject to change without notice
