3VA1116-6GD42-0AA0
Product ID:99398
Updated: 2026/4/3

Key Features
- 1Achieve superior short-circuit protection with a 70kA breaking capacity at 415V. 2、Ensure precise power distribution via selective protection with a 1:2.5 operational current interval. 3、Simplify installation in tight spaces with a compact 70mm cover size. 4、Enhance system safety using robust TM210 and FTFM line protection features. 5、Configure and maintain easily thanks to a flexible modular design with diverse accessories.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 70 | Rated Voltage(V): | 690 |
| Number of Poles: | 4P | Description | 3VA1H160 R160 TM210N F/4P; 3VA1_160 dimensions; Rated current 160A; Interrupting rating H:70kA; Trip unit TM210N; |
| Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM210N【LI fixed, with N-phase protection】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 70 | Interrupting Rating: | H:70kA |
| Rated Current In(A): | 160 | Specifications: | 160【1-160A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA1116-6GD42-0AA0 |
Specifications may be subject to change without notice