  • 1Achieve high breaking capacity (Icu=25 kA @ 415 V) for reliable system protection. 2、Utilize thermal-magnetic trip units for precise overload and short-circuit protection. 3、Simplify installation with modular, easy-to-fit internal accessories. 4、Save panel space with a compact 70 mm mounting depth. 5、Apply in AC/DC systems with no derating up to +50 °C.
Product Details
3VA1125-3EE42-0AA0
Siemens

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Rated Service Intermittent Breaking Capacity Ics(kA):@400V or 415V
25
Rated Voltage(V):
690
Number of Poles:
4P
Description
3VA1N160 R25 TM220 F/4P; 3VA1_160 dimensions; Rated current 25A; Interrupting rating N:25kA; Trip unit TM220;
Mounting Method:
F: Fixed
Trip Unit: (If required is not in the list, click reset, select trip unit first)
TM220 [L adjustable, I fixed]
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V
25
Interrupting Rating:
N:25kA
Rated Current In(A):
25
Specifications:
160 [1-160A]
Lifecycle
Delivery Release (PM300)
Country of Origin
China
ECCN
N
AL
N
Model Number
3VA1125-3EE42-0AA0