- 1Ensure reliable operation under high currents with a 70kA breaking capacity at 415V. 2、Provide comprehensive line protection using integrated TM240 and ATAM technology. 3、Deliver precise overload protection adjustable from 175A to 250A. 4、Offer robust short-circuit protection up to 10 times the nominal current. 5、Guarantee full safety with 100% neutral conductor protection and international compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 70 | Rated Voltage(V): | 690 |
| Number of Poles: | 4P | Description | 3VA1H250 R250 TM240N F/4P; 3VA1_250 dimensions; Rated current 250A; Interrupting rating H:70kA; Trip unit TM240N; |
| Mounting Method: | F: Fixed Mounting | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM240N【Thermal Magnetic Type LI】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 70 | Interrupting Rating: | H:70kA |
| Rated Current In(A): | 250 | Specifications: | 250【160-250A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA1225-6GF42-0AA0 |