3VA1450-4EF42-0AA0
Product ID:213752
Updated: 2026/4/6

Key Features
- 1Achieve high breaking capacity of 36 kA at 415V for maximum safety. 2、Utilize advanced TM240 and ATAM line protection technology for precision. 3、Configure overload protection with an adjustable range from 350A to 500A. 4、Save panel space with the compact IEC frame 630 design. 5、Rely on the proven thermal-magnetic trip unit for consistent reliability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 36 | Rated Voltage(V): | 690 |
| Number of Poles: | 4P | Description | 3VA1S630 R500 TM240 F/4P; 3VA1_630 dimensions; Rated current 500A; Interrupting rating S:36kA; Trip unit TM240; |
| Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, reset and select trip unit first) | TM240【Thermal Magnetic Type LI】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 36 | Interrupting Rating: | S:36kA |
| Rated Current In(A): | 500 | Specifications: | 630【400-630A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA1450-4EF42-0AA0 |
Specifications may be subject to change without notice