3VA2225-5JQ32-0AA0
Product ID:179921
Updated: 2026/4/14

Key Features
- 1Ensure reliable 55 kA short-circuit protection at 415V for maximum safety. 2、Achieve selective tripping with ETU560 for precise fault isolation. 3、Provide comprehensive LSIG line protection including ground fault monitoring. 4、Simplify installation in space-constrained panels with a compact, fixed design. 5、Enable energy monitoring with integrated metering functions for cost control.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 55 | Rated Voltage(V): | 690 |
| Number of Poles: | 3P | Description | 3VA2M250 R250 ETU560 F/3P; 3VA2_250 dimensions; Rated current 250A; Interrupting rating M:55kA; Trip unit ETU560; |
| Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, reset and select trip unit first) | ETU560【Electronic LSIG+LCD】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 55 | Interrupting Rating: | M:55kA |
| Rated Current In(A): | 250 | Specifications: | 250【160-250A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA2225-5JQ32-0AA0 |
Specifications may be subject to change without notice