3VA2463-6JQ42-0AA0

Product ID:201172
Updated: 2026/4/8
Siemens 3VA2463-6JQ42-0AA0

Key Features

  • 1Break short-circuit currents up to 85 kA at 415 V. 2、Utilize ETU560 LSIG protection for comprehensive system safety. 3、Adjust L, S, and G tripping parameters with customizable delays. 4、Install easily with a compact 70 mm depth and cover size. 5、Monitor ground faults and adjust protection settings as needed.
Product Details
3VA2463-6JQ42-0AA0
Siemens

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Rated Service Breaking Capacity Ics(kA): @400V or 415V
85
Rated Voltage(V):
690
Number of Poles:
4P
Description
3VA2H630 R630 ETU560 F/4P; 3VA2_630 dimensions; Rated Current 630A; Interrupting H:85kA; Trip Unit ETU560;
Mounting Method:
F: Fixed
Trip Unit: (If required is not in the list, click reset, select trip unit first)
ETU560 [Electronic LSIG + LCD]
Rated Ultimate Breaking Capacity Icu(kA): @400V or 415V
85
Interrupting Rating:
H:85kA
Rated Current In(A):
630
Specifications:
630 [400-630A]
Lifecycle
Delivery Release (PM300)
Country of Origin
China
ECCN
9N9999
AL
N
Model Number
3VA2463-6JQ42-0AA0

Specifications may be subject to change without notice