3VA2510-6HM42-0AA0
Product ID:196001
Updated: 2026/7/6

Key Features
- 1Deliver up to 85 kA at 415V for robust short-circuit protection.
- 2Suit three-phase networks, AC/DC applications, and 400 Hz operations.
- 3Optimize space with a compact 70 mm mounting depth.
- 4Integrate fully with standardized operation and installation methods.
- 5Enhance protection using thermal-magnetic and electronic trip units.
Need a quote? Enter your quantity and get pricing fast.
Qty
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Ics(kA)@690V: | 19 | Icu(kA)@690V: | 35 |
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 85 | Rated Voltage(V): | 415 |
| Number of Poles: | 4P | Description | 3VA2H1000 R1000 ETU330 F/4P; 3VA2_1000 dimensions; Rated Current 1000A; Interrupting Rating H:85kA; Trip Unit ETU330 |
| Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, reset and select trip unit first) | ETU330 [Electronic LIG] |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 85 | Interrupting Rating: | H:85kA |
| Rated Current In(A): | 1000 | Specifications: | 1000 [630-1000A] |
| Lifecycle | Delivery Release (PM300) | Country of Origin | Germany |
| ECCN | 9N9999 | AL | N |
| Model Number | 3VA2510-6HM42-0AA0 |
Specifications may be subject to change without notice