3VM1116-3EE42-0AA0
Product ID:152920
Updated: 2026/7/8

Key Features
- 1Achieve high breaking capacity up to 25 kA at 415 V AC.
- 2Utilize thermal-magnetic trip units for precise protection.
- 3Simplify installation with a modular design and standardized accessories.
- 4Save panel space with compact 70 mm depth and 45 mm cover.
- 5Ensure compliance with IEC 60947-1, 60947-2 standards.
Need a quote? Enter your quantity and get pricing fast.
Qty
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 18 | Rated Voltage(V): | 415 |
| Number of Poles: | 4P | Description | 3VM1N160 R160 TM220 F/4P; Size 160; Rated Current 160A; Interrupting Rating N:25kA; Trip Unit TM220; |
| Mounting Method: | F: Fixed Type | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM220【L adjustable, I fixed】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 25 | Interrupting Rating: | N:25kA |
| Rated Current In(A): | 160 | Specifications: | 160【8-160A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | N | AL | N |
| Model Number | 3VM1116-3EE42-0AA0 |
Specifications may be subject to change without notice