3VM1116-5ED32-0AA0
Product ID:193056
Updated: 2026/4/10

Key Features
- 1Ensure reliable protection with a high 55kA breaking capacity at 415V. 2、Meet strict safety standards by complying with IEC 60947-2. 3、Prevent system damage using advanced short-circuit protection. 4、Save panel space with a compact and efficient design. 5、Integrate easily across various control voltage applications.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 41 | Rated Voltage(V): | 415 |
| Number of Poles: | 3P | Description | 3VM1M160 R160 TM210 F/3P; Size 160; Rated Current 160A; Interrupting Rating M:55kA; Trip Unit TM210; |
| Mounting Method: | F: Fixed Mounting | Trip Unit: (If required is not in the list, click reset, then select the trip unit) | TM210【LI fixed, line protection】 |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 55 | Interrupting Rating: | M:55kA |
| Rated Current In(A): | 160 | Specifications: | 160【8-160A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | N | AL | N |
| Model Number | 3VM1116-5ED32-0AA0 |
Specifications may be subject to change without notice