Key Features
- 1Provide reliable line protection with thermal-magnetic trip units for AC/DC safety. 2、Save panel space using a compact design with 70mm depth. 3、Enhance system flexibility with modular accessories across the 3VM series. 4、Ensure robust short-circuit protection with a high 55 kA breaking capacity. 5、Meet industry standards including IEC 60947-1 and -2 for compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Service Breaking Capacity Ics(kA):@400V or 415V | 41 | Rated Voltage(V): | 415 |
| Number of Poles: | 3P | Description | 3VM1M160 R20 TM220 F/3P; Size 160; Rated Current 20A; Interrupting Rating M:55kA; Trip Unit TM220; |
| Mounting Method: | F: Fixed Type | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM220 [L adjustable, I fixed] |
| Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 55 | Interrupting Rating: | M:55kA |
| Rated Current In(A): | 20 | Specifications: | 160 [8-160A] |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | N | AL | N |
| Model Number | 3VM1120-5EE32-0AA0 |