3VM1332-5EE42-0AA0

Product ID:202577
Updated: 2026/4/8
Siemens 3VM1332-5EE42-0AA0

Key Features

  • 1Deliver reliable line protection with a 55 kA breaking capacity at 415V. 2、Ensure precise safety using advanced TM220 ATFM thermal-magnetic trip units. 3、Simplify installation in compact panels with a 248mm height and 138mm width. 4、Operate reliably in harsh conditions from -25°C to 70°C. 5、Meet global IEC 60947 standards for compliance and safety.
Product Details
3VM1332-5EE42-0AA0
Siemens

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Rated Service Breaking Capacity Ics(kA):@400V or 415V
41
Rated Voltage(V):
415
Number of Poles:
4P
Description
3VM1M400 R320 TM220 F/4P; Size 400; Rated Current 320A; Interrupting M:55kA; Trip Unit TM220;
Mounting Method:
F: Fixed
Trip Unit: (If required is not in the list, click reset, select trip unit first)
TM220【L adjustable, I fixed】
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V
55
Interrupting Rating:
M:55kA
Rated Current In(A):
320
Specifications:
400【250-400A】
Lifecycle
Delivery Release (PM300)
Country of Origin
China
ECCN
9N9999
AL
N
Model Number
3VM1332-5EE42-0AA0

Specifications may be subject to change without notice