3WT8252-6UG00-0AA1
Product ID:185304
Updated: 2026/4/20

Key Features
- 1Ensure safe operation with a high breaking capacity of 66 kA. 2、Combine all components modularly for easy adaptation. 3、Enhance safety with door sealing, signaling switch, and reclosing lockout. 4、Simplify planning and installation with a wide accessory range. 5、Conform to international standards like IEC 60947-2 and GB 14048.2.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Rated Voltage (V) | 500 | Description | 3WT2, 2500A ETU37WT F/3P, 66kA; Electric Operation Close AC/DC220V; Undervoltage Release AC/DC220V; Alarm Contacts; Door Frame; 2NO+2NC |
| Icw(kA) | 66 | Rated Service Short Circuit Breaking Capacity Ics(kA)@400V or 415V | 66 |
| Control Voltage | AC/DC220V | Number of Poles | 3P |
| Installation Method | F: Fixed Type | Trip Unit | ETU37WT【LSIG with LCD Display】 |
| Rated Current In(A) | 2500 | Rated Ultimate Breaking Capacity Icu(kA)@400V or 415V | 66 |
| Breaking Capacity Class | S:66kA | Specifications | 3WT2【630-4000A】 |
| Lifecycle | Delivery Release (PM300) | Country of Origin | China |
| ECCN | N | AL | N |
| Model Number | 3WT8252-6UG00-0AA1 |
Specifications may be subject to change without notice