Key Features

  • 1Accurate Electrical Measurements: Features Accuracy Class 1 for precise current transformation.
  • 2High Current Rating: Handles primary currents up to 400 A with a secondary rating of 5 A.
  • 3Compact Design: Includes a 3-meter cable with bare end flying leads for easy mounting.
  • 4Durable Construction: Rated for ambient temperatures from -10°C to +55°C.
  • 5Compliant with Standards: Meets industry standards for electrical measurement devices.

Need price and lead time?

Request a quote for original wago 855-5005/400-001. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original wago
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Protection type
IP20
Test voltage
AC 3?kV;?50?Hz;?1?min
Highest voltage for equipment U<sub>m</sub>
AC 720?Vrms
Feedthrough for measurement conductor
? 42 mm
Cable type
2 x 1.5 mm2; fine-stranded
Color code
black = S1; red = S2
Cable length
3m
Width
66.2 mm / 2.606 inches
Height
97 mm / 3.82 inches
Depth
66 mm / 2.6 inches
Mounting type
Split-core current transformer (suspended)
Weight
525.6g
Ambient temperature (operation)
-10 … +55 °C
Ambient temperature (storage)
-20 … +70 °C
Relative humidity
5 … 85?% (without condensation)
Operating altitude (max.)
2000m
Conformity marking
CE
Standards/specifications
EN 61869-1
Product Group
29 (INTERFACE ELECTRONIC (NET))
eCl@ss 10.0
27-21-09-02
eCl@ss 9.0
27-21-09-02
ETIM 9.0
EC002048
ETIM 8.0
EC002048
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
Box
Country of origin
NL
Customs tariff number
85043180888
RoHS Compliance Status
Compliant,No Exemption
Measured variable
Current
Rated continuous thermal current I<sub>cth</sub>
100 %
Rated short-time thermal current I<sub>th</sub>
60 x IN/ 1 s
Rated surge current I<sub>dyn</sub>
2.5 x Ith
Rated frequency
50 … 60?Hz
Primary rated current
400?A
Secondary rated current
5A
Rated power S<sub>r</sub>
0.5VA
Accuracy class
1